BULLETIN Vote - 'Scary Photos' Contest 2026

A Close-Up Look at the Dark Side of the Boiler Room
In the fall 2023 edition, we started a feature called Scary Photos, and National Board Commissioned Inspectors are invited to submit photos of the problems they witness during everyday inspections to serve as a warning for what to look for in the field.

Once a year, readers will vote on the “scariest” photo from all the submissions, and now is the time! Below are the six Scary Photos published in the last three editions. The inspector who submitted the winning photo will receive a $100 gift card.

Contact Lee Cochran, senior editor, at lcochran@nationalboard.org with questions.

Read the descriptions below the photos, and then vote for the "scariest" photo. Only one vote per person.

Voting ends December 31, 2026.
Click an image to select your choice for "scariest" photo. Then click the "Submit" button at the bottom of the page to cast your vote.(Required.)
  • SUBMISSION #1: The low-pressure hot water firetube boiler served as a backup for a wastewater treatment plant and was rarely utilized. However, when used, it burned digester gas. In the mid-1990s, a design change was approved for several tubes to be eliminated to reduce the heating surface from 400 square feet to 273 square feet. This prevented adequate operation with the return temperature of the boiler fluid being below the dew point of the digester gas, resulting in the boiler experiencing extensive corrosion on the tube sheet and around the tube sheet to shell welds. The owner replaced it with two smaller boilers.
  • SUBMISSION #2: An external inspection revealed a pressure relief valve installed backward on an operational cast-iron-boiler. The boiler was immediately removed from service, and a contractor correctly installed the valve within a few hours.
  • SUBMISSION #3: A boiler was found leaking steam; however, a company official refused to shut it down and asked the inspector to leave the premises. A supervising inspector arrived and red-tagged the boiler, which was later repaired by an R stamp company and returned to service.
  • SUBMISSION #4: Some air tanks were manufactured with an internal dip tube for draining condensate, and they are easy to identify because the drain valve is located around the 7 to 8 o’clock position on the tank. The problem is that the dip tube can’t drain all the condensate. The tank was removed from service after eight years due to low ultrasonic readings. The business owner said the tank was like “new,” so the owner was asked to remove the inspection plug at the end of the head to allow for an internal inspection, which identified the problem. The owner was required to move the drain valve to the lowest point where condensate can collect. Most but not all tanks also have a plugged drain at the 6 o’clock position. It is the understanding of the inspector that the practice of installing a dip tube has now stopped, but was common practice for at least 20 years.
  • SUBMISSION #5: During external inspections of jurisdictional objects, it was noted that the T&P valve on a non-jurisdictional hot water storage tank was corroded. The client attempted to lift the valve to verify mechanical operation, but the valve disc had completely detached from the stem. The hot water storage tank was immediately removed from service, and the valve was replaced.
  • SUBMISSION #6: Because of an unsightly sight glass, this boiler was taken out of service until a new sight glass and seals were installed.